Thông tin tài liệu
OptiX OSN 3500
Installation Manual Contents
Contents
3 Installing a Cabinet on
the Antistatic Floor 1
3.1 Installation Flow and Expected Result 2
3.1.1 Installation Flow 2
3.1.2 Expected Result 3
3.2 Positioning the Cabinet 4
3.2.1 Positioning a Cabinet Independently 4
3.2.2 Positioning a Cabinet Close to an Installed Cabinet 5
3.2.3 Positioning Cabinets Abreast 6
3.2.4 Positioning Cabinets Back to Back 7
3.2.5 Checking the Positioning 7
3.3 Positioning the Support 8
3.3.1 Types of the Support 8
3.3.2 Positioning the Support on the Floor 9
3.4 Installing the Support 10
3.5 Installing the Cabinet on the Support 12
3.6 Checking the Cabinet Installation 15
Issue 05 (2006-11-20)
Huawei Technologies Proprietary
i
OptiX OSN 3500
Installation Manual Figures
Figures
Installation flow of installing a cabinet on the antistatic floor 2
Cabinet installed on the antistatic floor 3
Positioning a cabinet independently 4
Positioning a cabinet close to an installed cabinet 5
Positioning cabinets abreast 6
Positioning cabinets back to back 7
S300A support 8
Mounting holes for the support (a single cabinet) 9
Installing the expansion tube and expansion nut 10
Fixing the support on the floor 11
Placing the cabinet and the insulation plates 12
Leveling the cabinet 13
Securing the cabinet on the support 14
Installing the floor pallet 15
Issue 05 (2006-11-20)
Huawei Technologies Proprietary
iii
OptiX OSN 3500
Installation Manual Tables
Tables
Figure 1.1Types of the support 8
Issue 05 (2006-11-20)
Huawei Technologies Proprietary
v
OptiX OSN 3500
Installation Manual
3 Installing a Cabinet on
the Antistatic Floor
3 Installing a Cabinet on
the Antistatic Floor
About This Chapter
When the installation is well prepared, install the cabinet. There are three modes
for installing the cabinet according to the floor of the equipment room.
Installation on the antistatic floor
Installation on the cement floor (see Chapter 4 "Installing a cabinet on the
Cement Floor")
Installation on the wooden floor (the same as the installation on the cement
floor)
This chapter guides you to install the cabinet on the antistatic floor. We
recommend reading OptiX OSN 3500 Intelligent Optical Transmission System
Compliance and Safety Manual. This helps you to ensure a safe and smooth
installation.
The following table lists the contents of this chapter.
Section Description
3.1Installation Flow and
Expected Result
Describes the installation flow.
3.2Positioning the Cabinet Describes operations and procedures of marking
the installation position for the cabinet.
3.3Positioning the Support Describes operations and procedures of marking
the position for the support.
Issue 05 (2006-11-20)
Huawei Technologies Proprietary
1
3 Installing a Cabinet on
the Antistatic Floor
OptiX OSN 3500
Installation Manual
Section Description
3.4Installing the Support Describes operations and procedures of installing
the support.
3.5Installing the Cabinet on the
Support
Describes operations and procedures of installing
the cabinet on the support.
3.6Checking the Cabinet
Installation
Describes the check points of the installation.
3.1 Installation Flow and Expected Result
This section describes the installation flow and expected installation result.
3.1.1 Installation Flow
Figure 1.1 shows the installation flow for cabinet installation on the antistatic
floor.
Starting
Positioning the cabinet
End
Positioning the support
Installing the support
Installing the cabinet on the
support
Checking the installation
Figure 1.1 Installation flow of installing a cabinet on the antistatic floor
2
Huawei Technologies Proprietary
Issue 05 (2006-11-20)
OptiX OSN 3500
Installation Manual
3 Installing a Cabinet on
the Antistatic Floor
3.1.2 Expected Result
Figure 1.1 shows the expected result of a cabinet installed on the antistatic floor.
Cabinet
Antistatic floor
Figure 1.1 Cabinet installed on the antistatic floor
Note
There is no antistatic floor between the cabinet and the support.
Note
To install multiple cabinets of the same type side by side, you only need to install
the side doors at two ends of the row of cabinets.
Issue 05 (2006-11-20)
Huawei Technologies Proprietary
3
3 Installing a Cabinet on
the Antistatic Floor
OptiX OSN 3500
Installation Manual
3.2 Positioning the Cabinet
This section guides you to mark the installation position for the cabinet on the
antistatic floor. The position varies with the number of cabinets and their layout.
3.2.1 Positioning a Cabinet Independently
Purpose
This procedure guides you to position a cabinet which is
installed independently.
Tools /Materials
Pencil
Ruler
Prerequisites
The cabinet and the accessories (including the support and
fixing pieces) have been transported to the site.
Required/As needed
Required if the cabinet is installed independently.
Caution
Read technical documents on construction before you mark the installation
position for the cabinet.
Step 1 Mark the reference point for installing the cabinet according to the construction
drawing.
Step 2 Draw a 600 mm x 300 mm rectangle according to the reference point. See Figure
1.1.
600mm
300mm
800mm
≥
Reference point
the wall
Front of cabinet
≥
1000mm
Figure 1.1 Positioning a cabinet independently
4
Huawei Technologies Proprietary
Issue 05 (2006-11-20)
OptiX OSN 3500
Installation Manual
3 Installing a Cabinet on
the Antistatic Floor
End
3.2.2 Positioning a Cabinet Close to an Installed Cabinet
Purpose
This procedure guides you to position a cabinet close to an
installed cabinet.
Tools /Materials
Pencil
Ruler
Plummet
Prerequisites
The cabinet and the accessories (including the support and
fixing pieces) have been transported to the site.
Required/As needed
Required if the cabinet is installed close to an installed
cabinet.
Step 1 Use a plummet to determine and mark the side projective position (on the ground)
of the installed cabinet.
Step 2 Draw the side outline of the cabinet to be installed according to the marks made in
step 1.
Step 3 Draw the front outline of the cabinet to be installed according to the front outline
of the cabinet already installed.
Step 4 Mark the installation reference point.
Step 5 Draw a 600 mm x 300 mm rectangle as shown in Figure 1.1 according to the
reference point, and then draw the central lines for the cabinet.
600mm
300mm
1 2 3 45
1. Front outline of the cabinet to be installed 2. Central lines of the cabinet to be installed
3. Side outline of the cabinet to be installed 4. Layout of the cabinet already installed
5. Reference point
Figure 1.1 Positioning a cabinet close to an installed cabinet
End
Issue 05 (2006-11-20)
Huawei Technologies Proprietary
5
3 Installing a Cabinet on
the Antistatic Floor
OptiX OSN 3500
Installation Manual
3.2.3 Positioning Cabinets Abreast
According to Figure 1.1, mark the position of cabinets.
≥ 1000mm
Inner corner
≥ 800mm
≥ 1000mm
≥ 1000mm
Cabinet
600mm
300mm
Plan view of cabinets
Figure 1.1 Positioning cabinets abreast
6
Huawei Technologies Proprietary
Issue 05 (2006-11-20)
OptiX OSN 3500
Installation Manual
3 Installing a Cabinet on
the Antistatic Floor
3.2.4 Positioning Cabinets Back to Back
According to Figure 1.1, mark the position of cabinets back to back.
≥ 1000mm
Inner corner
≥ 800mm
≥ 1000mm
≥ 1000mm
Cabinet
600mm
300mm
Plan view of cabinets
Front of cabinet
Front of cabinet
Front of cabinet
600mm
300mm
Figure 1.1 Positioning cabinets back to back
3.2.5 Checking the Positioning
Check the positioning as the following items.
The minimum distance between two rows of cabinets is 1 m.
The minimum distance between the cabinet side and the wall is 0.8 m.
The minimum distance between the front/back of the cabinet and the wall is 1
m.
An aisle at least 1 metre wide is reserved in the equipment room.
The cable outlet on the top of the cabinet is aligned with the lower part of the
cabling trough of the equipment room.
The position for installing the cabinet is correct and meets the requirements in
the construction drawing.
Issue 05 (2006-11-20)
Huawei Technologies Proprietary
7
[...]... 2 Place the cabinet on the plates with the holes aligned from the top down See Figure 1.1 Insulation plate Figure 1.1 Placing the cabinet and the insulation plates 12 Huawei Technologies Proprietary Issue 05 (2006-11-20) OptiX OSN 3500 Installation Manual 3 Installing a Cabinet on the Antistatic Floor Step 3 Adjust the levelness of the cabinet by adding washers between the insulation plates and the. .. Installation Manual 3 Installing a Cabinet on the Antistatic Floor 3.3.2 Positioning the Support on the Floor Purpose This procedure guides you to position the support on the floor after positioning the cabinet Tools /Materials Pencil Ruler Prerequisites The cabinet has been positioned Required/As needed Required if the cabinet is installed on the antistatic floor Step 1 Draw a 460 mm x 264 mm rectangle... install the cabinet on the support Tools /Materials Horizontal ruler M12 x 40 bolt Insulation plate Washer Prerequisites The support has been installed Required/As needed Required if the cabinet is installed on the antistatic floor Caution At least three persons are required to install the cabinet on the support Step 1 Place the two insulation plates on the support with the holes aligned from the top... Measure the resistance between the support and the cabinet The normal resistance should be larger than 5 megaohm If the measured resistance is less than 5 megaohm, demount the cabinet and check the insulation components Then repeat the operations from step 1 If the measured resistance is larger than 5 megaohm, continue to the next step Step 8 Fix the horizontal pallet and side pallet to the support...3 Installing a Cabinet on the Antistatic Floor OptiX OSN 3500 Installation Manual 3.3 Positioning the Support This section describes how to position the support in the equipment room An S30 0A support assembly is used to support the cabinet It also facilitates floor installation and cabling Each cabinet needs one S30 0A support assembly ("support" hereinafter) 3.3.1 Types of the Support Figure... Horizontal pallet 2 Side pallet 5 Cabinet 3 Support Figure 1.1 Installing the floor pallet Step 9 Cut and restore the antistatic floor according to the circumstance around the cabinet End 3.6 Checking the Cabinet Installation The following requirements should be met when the support is installed properly The position of the cabinet is consistent with the engineering design drawing The installation... Proprietary Issue 05 (2006-11-20) OptiX OSN 3500 Installation Manual 3 Installing a Cabinet on the Antistatic Floor Step 5 Drive the expansion tube completely into the floor with a rubber hammer Step 6 Repeat steps 2–5 to install the other three expansion tubes and expansion nuts Step 7 Use height adjusting screws to level the height indicator on the support with the height of the antistatic floor See... frame of the cabinet, and into the connecting hole of the support See Figure 1.1 Issue 05 (2006-11-20) Huawei Technologies Proprietary 13 3 Installing a Cabinet on the Antistatic Floor OptiX OSN 3500 Installation Manual M12X40 bolt Insulation washer Figure 1.1 Securing the cabinet on the support Step 6 Tighten the bolts alternately to reduce the stress between the bolts and the cabinet Step 7 Measure... Figure 1.1 Caution If the washers are not inserted between the insulation plates and the support, insulation between the cabinet and the floor cannot be guaranteed Washer Figure 1.1 Leveling the cabinet Step 4 On the top of the cabinet, place the level instrument in two perpendicular directions to check the levelness of the cabinet Step 5 Vertically insert the M12 x 40 bolt assembly through the lower... 2 Remove the expansion tube and nut from the expansion bolt Step 3 Insert the guide rib on the expansion nut into the guide slot on the expansion tube Step 4 Put the expansion tube and nut vertically into the hole, as shown in Figure 1.1 Bolt Expansion tube Guide slot on expansion tube Expansion nut Guide rib on expansion nut Figure 1.1 Installing the expansion tube and expansion nut 10 Huawei Technologies . 3500
Installation Manual
3 Installing a Cabinet on
the Antistatic Floor
3.2.4 Positioning Cabinets Back to Back
According to Figure 1.1, mark the position of cabinets. installing the cabinet according to the floor of the equipment room.
Installation on the antistatic floor
Installation on the cement floor (see Chapter
Ngày đăng: 19/01/2014, 10:20
Xem thêm: Tài liệu Installing a Cabinet on the Antistatic Floor doc, Tài liệu Installing a Cabinet on the Antistatic Floor doc, Step 5 Draw a 600 mm x 300 mm rectangle as shown in Figure 1.1 according to the reference point, and then draw the central lines for the cabinet., Step 4 Put the expansion tube and nut vertically into the hole, as shown in Figure 1.1.