ASTM D120-22 Standard Specification for Rubber Insulating Gloves

9 0 0
ASTM D120-22 Standard Specification for Rubber Insulating Gloves

Đang tải... (xem toàn văn)

Thông tin tài liệu

Chemical and Physical Requirements10.1 Glove test material taken from sample gloves selectedin accordance with13.3shall conform to physical requirementsinTable 5and the accelerated aging

This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee Designation: D120 − 22 Standard Specification for Rubber Insulating Gloves1 This standard is issued under the fixed designation D120; the number immediately following the designation indicates the year of original adoption or, in the case of revision, the year of last revision A number in parentheses indicates the year of last reapproval A superscript epsilon (´) indicates an editorial change since the last revision or reapproval This standard has been approved for use by agencies of the U.S Department of Defense 1 Scope D297 Test Methods for Rubber Products—Chemical Analy- sis 1.1 This specification covers manufacturing and testing of rubber insulating gloves for protection of workers from elec- D412 Test Methods for Vulcanized Rubber and Thermoplas- trical shock tic Elastomers—Tension 1.2 Two types of gloves are provided and are designated as D573 Test Method for Rubber—Deterioration in an Air Type I, non-resistant to ozone, and Type II, resistant to ozone Oven 1.3 Six classes of gloves, differing in electrical D624 Test Method for Tear Strength of Conventional Vul- characteristics, are provided and are designated as Class 00, canized Rubber and Thermoplastic Elastomers Class 0, Class 1, Class 2, Class 3, and Class 4 D1415 Test Method for Rubber Property—International 1.4 The values stated in SI units are to be regarded as Hardness standard The values given in parentheses after SI units are provided for information only and are not considered standard D2240 Test Method for Rubber Property—Durometer Hard- See IEEE/ASTM SI 10 ness 1.5 The following safety hazards caveat pertains only to the F819 Terminology Relating to Electrical Protective Equip- test method portion, Sections 16, 17, 18, and 19, of this ment for Workers specification: This standard does not purport to address all of the safety concerns, if any, associated with its use It is the IEEE/ASTM SI 10 American National Standard for Metric responsibility of the user of this standard to establish appro- Practice priate safety, health, and environmental practices and deter- mine the applicability of regulatory limitations prior to use 3 Terminology For a specific warning statement, see 18.2 3.1 Definitions: 1.6 This international standard was developed in accor- 3.1.1 color splash—a splash, smear, or streak of contrasting dance with internationally recognized principles on standard- color evident on the inside or outside surface of the gloves that ization established in the Decision on Principles for the was deposited during the dipping operation and is vulcanized Development of International Standards, Guides and Recom- into the glove as part of the homogenous compound mendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee 3.1.2 glove cuff roll—the roll or reinforced edge of an insulating glove at the cuff 2 Referenced Documents 2.1 ASTM Standards:2 3.1.3 halogenation treatment—exposure of the entire glove surface area to a halogen for the purpose of reducing surface 1 This specification is under the jurisdiction of ASTM Committee F18 on friction Electrical Protective Equipment for Workers and is the direct responsibility of Subcommittee F18.15 on Worker Personal Equipment This standard replaces ANSI 3.1.4 ozone—a very active form of oxygen that may be Standard J 6.6, which is no longer available produced by corona, arcing, or ultraviolet rays Current edition approved Feb 1, 2022 Published March 2022 Originally 3.1.5 user—the employer or entity purchasing the equip- approved in 1921 Last previous edition approved in 2021 as D120 – 21 DOI: ment to be utilized by workers for their protection; in the 10.1520/D0120-22 absence of such an employer or entity, the individual purchas- ing and utilizing the protective equipment 2 For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org For Annual Book of ASTM 3.1.6 working area—all finger and thumb crotches, the palm Standardsvolume information, refer to the standard’s Document Summary page on (area between the wrist and the base of the finger and thumb) the ASTM website and the area of the finger and thumb facing the palm not extending beyond the center line of the crotch See Fig 1 3.1.7 For definitions of other terms, refer to Terminology F819 Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959 United States 1 D120 − 22 FIG 1 Working Area of a Rubber Insulating Glove TABLE 1 Proof-Test/Use Voltage Relationship 4.4 It is common practice and the responsibility of the user of this type of protective equipment to prepare complete AC Proof-Test Maximum AC DC Proof-Test Maximum DC Use instructions and regulations to govern the correct and safe use Class of Glove Voltage, rms, V Use Voltage ac Voltage, avg, V Voltage avg, V of such equipment rms, V 5 Classification 00 2 500 500 10 000 750 5.1 Gloves covered under this specification shall be desig- nated as Type I or Type II; Class 00, Class 0, Class 1, Class 2, 0 5 000 1 000 20 000 1 500 Class 3, or Class 4 1 10 000 7 500 40 000 11 250 5.1.1 Type I, non-resistant to ozone, made from a high-grade cis-1,4-polyisoprene rubber compound of natural or synthetic 2 20 000 17 000 50 000 25 500 origin, properly vulcanized 3 30 000 26 500 60 000 39 750 5.1.2 Type II, ozone-resistant made of any elastomer or combination of elastomeric compounds 4 40 000 36 000 70 000 54 000 5.1.3 The class designation shall be based on the electrical 4 Significance and Use properties as shown in Table 2 and Table 3 4.1 This specification covers the minimum electrical, 6 Ordering Information chemical, and physical properties guaranteed by the manufac- turer and the detailed procedures by which such properties are 6.1 Orders for gloves under this specification should include to be determined The purchaser has the option to perform or the following information: have performed any of these tests in order to verify the guarantee Claims for failure to meet the specification are 6.1.1 Type, subject to verification by the manufacturer 6.1.2 Class, 6.1.3 Length, Fig 2 4.2 Gloves are used for personal protection; therefore, when 6.1.4 Size, authorizing their use, a margin of safety shall be allowed 6.1.5 Color, between the maximum voltage on which they are used and the 6.1.6 Cuff design, and proof-test voltage at which they are tested The relationship 6.1.7 With or without a halogenation treatment between proof-test voltage and the maximum voltage at which the gloves shall be used is shown in Table 1 6.2 The listing of types, classes, lengths, sizes, colors, and cuff designs is not intended to mean that all shall necessarily be 4.3 Work practices vary from user to user and are dependent available from manufacturers; it signifies only that, if made, upon many factors These may include, but are not limited to, they shall conform to the details of this specification operating system voltages, construction design, work proce- dure techniques, weather conditions, and so forth Therefore, except for the restriction set forth in this specification because of design limitations, the use and maintenance of this equip- ment is beyond the scope of this specification 2 D120 − 22 TABLE 2 AC Voltage Requirement Proof Test CurrentsA Proof-Test Minimum Maximum Proof-Test Current, mA Voltage, Breakdown Class of rms, V 280 mm 360 mm 410 mm 460 mm Glove Voltage, (11-in.) Glove (14-in.) Glove (16-in.) Glove (18-in.) Glove rms, V 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 HZ 00 2 500 4 000 6.7 8 10 12 B B B B 0 5 000 6 000 6.7 8 10 12 11.7 14 13.3 16 1 10 000 20 000 11.7 14 13.3 16 15 18 2 20 000 30 000 13.3 16 15 18 16.7 20 3 30 000 40 000 15 18 16.7 20 18.3 22 4 40 000 50 000 18.3 22 20 24 A Proof test current shall be measured to an accuracy of ±1 mA B Not applicable TABLE 3 DC Voltage Requirements 8.3.1 Standard lengths for Class 00 gloves are 280 mm (11 in.), and 360 mm (14 in.) The permissible variations shall be Class of Glove Proof-Test Minimum Breakdown 613 mm (61⁄2 in.) Voltage avg V Voltage avg V 8.3.2 Standard lengths for Class 0 gloves are 280 mm (11 00 10 000 13 000 in.), 360 mm (14 in.), 410 mm (16 in.), and 460 mm (18 in.) The permissible variations shall be 613 mm (61⁄2 in.) 0 20 000 35 000 8.3.3 Standard lengths for Class 1, 2, and 3 gloves are 360 1 40 000 60 000 mm (14 in.), 410 mm (16 in.), and 460 mm (18 in.) The permissible variation shall be 613 mm (61⁄2 in.) 2 50 000 70 000 8.3.4 Standard lengths for Class 4 gloves are 410 mm (16 3 60 000 80 000 in.) and 460 mm (18 in.) The permissible variation shall be 613 mm (61⁄2 in.) 4 70 000 90 000 9 Workmanship and Finish 7 Manufacture and Marking 9.1 Gloves shall be free on both inner and outer surface of 7.1 The gloves shall be produced by a seamless process harmful physical irregularities that can be detected by thorough test and inspection 7.2 The gloves shall have a smooth finish and the cuff edges shall be finished with a roll or a reinforcing strip of rubber, 9.1.1 Harmful physical irregularities may be defined as any unless otherwise specified feature that disrupts the uniform, smooth surface contour and represents a potential hazard to the user, such as pinholes, 7.3 Each glove shall be marked clearly and permanently cracks, blisters, cuts, conductive embedded foreign matter, with the name of the manufacturer or supplier, ASTM D120, creases, pinch marks, voids (entrapped air), prominent ripples, type, class, and size All such marking shall be confined to the and prominent mold marks cuff portion of the glove and shall be nonconducting and applied in such a manner as to not impair the required 9.2 Nonharmful physical irregularities may be defined as properties of the glove surface irregularities present on the inner and outer surfaces of the rubber glove due to imperfections on forms or molds and 7.3.1 Each glove shall be marked with a label that gives the inherent difficulties in the manufacturing process These irregu- information specified in 7.3 This label shall be the color larities may appear as mold marks that look like cuts even specified for each voltage class: Class 00—beige, Class though they are actually a raised ridge of rubber, indentations, 0—red, Class 1—white, Class 2—yellow, Class 3—green, and protuberances, embedded foreign material, or color splashes Class 4—orange that are acceptable provided that: 7.4 At the request of the user, the gloves may be given a 9.2.1 The indentations, protuberance or mold marks tend to halogenation treatment to reduce surface friction This treat- blend into a smooth slope upon stretching of the material ment shall have no detrimental effect on the electrical, chemical, or physical properties of the gloves 9.2.2 The rubber thickness at any irregularity conforms to the thickness requirements 8 Dimensions and Permissible Variations 9.2.3 Foreign material remains in place when the glove is 8.1 Sample gloves selected in accordance with 13.2 shall folded and stretched with the material surrounding it fall within the thickness limits specified in Table 4, when determined in accordance with 17.1 9.2.4 Color splashes are no larger than 1 mm in any direction on the inner surface of the work area 8.2 Sample gloves selected in accordance with 13.2 shall conform to standard sizes when determined in accordance with 9.2.4.1 The working area is defined as all finger and thumb 17.2 Standard sizes are 203 mm (8 in.), 216 mm (81⁄2 in.), 229 crotches, the palm (area between the wrist and the base of the mm (9 in.), 241 mm (91⁄2 in.), 254 mm (10 in.), 267 mm (101⁄2 finger and thumb) and the area of the finger and thumb facing in.), 279 mm (11 in.), 292 mm (111⁄2 in.), and 305 mm (12 in.) the palm not extending beyond the center line of the crotch The permissible variation in size shall be 613 mm (61⁄2 in.) See Fig 1 8.3 Sample gloves selected in accordance with 13.2 shall conform to standard lengths when measured in accordance with 17.3 3 D120 − 22 FIG 2 Length and Contour Measurements on Contour Cuff Gloves TABLE 4 Thickness Measurements 11 Electrical Requirements Minimum Thickness Maximum Thickness 11.1 Each glove shall be given a proof test and shall withstand the 50-Hz or 60–Hz AC proof-test voltage (rms Class of In Crotch Other Than Crotch value) or the dc proof-test voltage (average value) specified in Glove Table 2 or Table 3 The proof test shall be performed in mm in mm in mm in accordance with Section 18 The test voltage shall be applied 00 continuously for 3 min 0 0.20 0.008 0.25 0.010 0.75 0.030 1 11.1.1 When the ac proof test is used, the 60-Hz proof-test 2 0.46 0.018 0.51 0.020 1.02 0.040 current shall not exceed the values specified in Table 2 at any 3 time during the test period (Note 1) 4 0.63 0.025 0.76 0.030 1.52 0.060 11.2 Sample gloves selected in accordance with 13.2 shall 1.02 0.040 1.27 0.050 2.29 0.090 not break down at voltages below those specified in Table 2 or Table 3 when tested in accordance with Section 18 1.52 0.060 1.90 0.075 2.92 0.115 11.2.1 Gloves that have been subjected to a minimum 2.03 0.080 2.54 0.100 3.56 0.140 breakdown voltage test shall not be used for electric protection Proof test current shall be measured to an accuracy of 61 mA 10 Chemical and Physical Requirements 11.3 Sample gloves selected in accordance with 13.2 shall 10.1 Glove test material taken from sample gloves selected be subjected to a 50-Hz or 60–Hz AC moisture absorption/ in accordance with 13.3 shall conform to physical requirements proof test in accordance with Section 18 in Table 5 and the accelerated aging in 19.2.6 11.3.1 The 50-Hz or 60–Hz AC proof test current shall not 10.2 In the event of a dispute, the identification of the rubber exceed the values specified in Table 2 by more than 2 mA polymer in Type I gloves shall be performed in accordance with 19.1 NOTE 1—A proof-test current is an indication of the validity of the glove make-up, the dielectric constant of the type of material used, the 10.3 Type II glove test material taken from sample gloves thickness, and the total contact area under test selected in accordance with 13.3 shall show no visible effects of ozone when tested in accordance with 18.6 Any visible 12 Guarantee signs of ozone deterioration of the glove material, such as checking, cracking, breaks, pitting, and so forth, shall be 12.1 The manufacturer or supplier shall replace, without considered as evidence of failure to meet the requirements of charge to the purchaser, unused gloves which, at any time Type II gloves within a period of nine (9) months from date of initial delivery of shipment to the purchaser or his designee, fail to pass the TABLE 5 Physical Requirements tests in this specification This guarantee will be binding on the manufacturer or supplier only if the gloves have been properly Property Type I Type II stored and have not been subjected to more than an original acceptance test and one retest Tensile strength, min, Die C, MPa (psi) 17.2 (2500) 10.3 (1500) Tensile stress at 200 %, max, MPa (psi) 2.1 (300) 2.1 (300) Ultimate elongation, min, % 600 500 Tension set, max at 400, % 25 25 Tear resistance, min, kN/m (lbf/in.) 21 (120) 14 (80) Puncture resistance, min, kN/m (lbf/in.) 18 (100) 18 (100) Hardness, max, shore A 47 47 4 D120 − 22 12.2 Any acceptance test made by the purchaser, or the been furnished, the manufacturer or supplier may request that purchaser’s designee, shall be performed within the first two his representative witness the testing of additional gloves from (2) months of the guarantee period unless otherwise specified the shipment NOTE 2—Proper storage means that gloves are stored right side out, not 14.5 The entire lot or shipment may be rejected at the option distorted and not stored directly above or in proximity to steam pipes, of the purchaser if two specimens of the first sample and one radiators, or other sources of artificial heat, or exposed to direct sunlight of the second sample, selected in accordance with 13.3, fail any or other sources of ozone It is desirable that the ambient storage of the separate requirements outlined in Section 10 temperature shall not exceed 35 °C (95 °F) 14.6 The entire lot or shipment of gloves may be rejected at 13 Sampling the option of the purchaser if 25 % of the gloves in the lot or shipment fail to meet the requirements of Section 8 or 9 13.1 Each glove in a lot or shipment shall be subjected to inspection and test to meet the requirements of Sections 7, 14.7 All rejected material shall be returned as directed by 11.1, 9, and 15 the manufacturer, at his or the supplier’s request, without being defaced by rubber stamp or other permanent marking 13.2 An original sample of 1 % of the lot or shipment or not However, those gloves punctured when tested in accordance less than two gloves, whichever is greater, shall be selected at with 11.1, 11.2, and 11.3 shall be stamped, punched, or cut random from the lot or shipment for the test requirements of prior to being returned to the supplier to indicate that they are 11.2, 11.3 and Section 8 Where a failure occurs in the first unfit for electrical use sample, a second sample of the same quantity shall be selected and tested 15 Packaging and Package Marking 13.3 An original sample of 0.1 % of the lot or shipment or 15.1 Each pair of gloves shall be packaged in an individual not less than two gloves, whichever is greater, shall be selected container of sufficient strength to properly protect the gloves at random from the lot or shipment for the test requirements of from damage in transit The end of the container shall be Sections 10.1 and 10.3 marked with the name of the manufacturer or supplier, type, class, length, size, color, and cuff design 14 Rejection TEST METHODS 14.1 Individual gloves shall be rejected if they fail to meet the requirements of Sections 7, 9 and 11.1 and the minimum 16 Sequence of Testing thickness requirements of 8.1 16.1 The following order of procedure is suggested for 14.2 Individual gloves may be rejected at the option of the testing rubber insulating gloves: purchaser if they fail to meet the requirements of Sections 8 and 15 16.1.1 Inspection of the surfaces in accordance with Section 9 14.3 The entire lot or shipment of gloves shall be rejected under any of the following conditions: 16.1.2 The dimensions in accordance with Section 17 16.1.3 Electrical proof tests in accordance with 18.4.2 or 14.3.1 If 5 % or more, but not less than two gloves, in a lot 18.5.2 or shipment fail to meet the requirements of 11.1 16.1.4 AC moisture absorption/proof test in accordance with 18.4.4 14.3.2 If two gloves in the first sample fail to meet the 16.1.5 Breakdown voltage tests in accordance with 18.4.3 requirements of 11.2 or 18.5.3 16.1.6 Ozone resistance tests in accordance with 18.6 14.3.3 If one glove in the original sample and one or more 16.1.7 Chemical and physical property tests in accordance gloves in the second sample fail to meet the requirements of with Section 19 11.2 17 Dimension Measurements 14.3.4 If the sample of Type II gloves, using the sampling methods of 13.3, fails to meet the requirements of 10.3 17.1 Thickness: 17.1.1 Thickness measurements shall be made at four or 14.3.5 If the proof test current on two gloves in the first more points on the palm side, four or more points on the back sample do not meet the requirements of 11.3 side, one or more points in the crotch of the thumb and index finger, and one or more points in the crotches between the 14.3.6 If the proof test current on one glove in the original fingers See Table 4 sample and the proof test current on one or more gloves in the 17.1.2 Thickness measurements shall be made on complete second sample fail to meet the requirements of 11.3 gloves with a micrometer graduated to within 0.025 mm (0.001 in.), having an anvil about 6 mm (0.25 in.) in diameter and a 14.4 The testing shall be terminated and the manufacturer or presser foot of 3.17 mm 6 0.25 mm (0.125 in 6 0.010 in.) in supplier notified if, during the course of testing, the gloves in diameter The presser foot shall exert a total force of 0.83 N 6 a lot or shipment fail to meet the requirements of 10.3, 11.1, 0.03 N (3.0 ozf 6 0.1 ozf) 11.2, or 11.3 as determined by the rejection criteria of 14.3.1, 14.3.2, 14.3.314.3.4, 14.3.5, or 14.3.6 The manufacturer or NOTE 3—A dial-type micrometer graduated in millimetres or inches and supplier may in such a case require the purchaser to submit proof that the test procedure and equipment conform to the appropriate paragraphs of Section 18 When such proof has 5 D120 − 22 mounted in a manner similar to that shown in Fig 3 and Fig 4 is particularly convenient for making these measurements 17.1.3 Make sample test specimen thickness measurements with a similar micrometer, except that the anvil shall be at least 38 mm (1.5 in.) in diameter or, if having a smaller anvil, be provided with equivalent means of supporting the specimen in a flat position In addition, the presser foot shall be 6.3 mm 6 0.3 mm (0.25 in 6 0.010 in.) in diameter 17.2 Size shall be the interior circumference of the glove measured on a line parallel to the finger crotches and passing through the thumb crotch The method of determining this dimension shall be to measure the outside width, W, at this line with the hand of the glove in a flattened state, subtract twice the median glove thickness, T, in the hand, and multiply this difference by a factor of 2: S 5 2 ~W 2 2T! where: S = size of the glove, W = outside width, and T = median glove thickness 17.3 Length: 17.3.1 Length shall be measured with the glove in a relaxed position and the edge of the cuff perpendicular to the line of measurement Length is the distance from the tip of the second finger to the outside edge of the cuff as shown in Fig 2 and Fig 5 17.3.2 Measure the difference in lengths for contour cuff gloves with the glove in the same position and along a line parallel to the length dimensions, as shown in Fig 2 FIG 4 Dial-Type Micrometer for Measuring Glove Thickness at Fingertips FIG 3 Dial-Type Micrometer for Measuring Glove Thickness 6 D120 − 22 FIG 5 Length Measurement on Standard Cuff Glove 18 Electrical Tests voltage The test apparatus or each position, or both, should be protected by an automatic circuit-breaking device designed to 18.1 All electrical tests shall be performed at room tempera- open promptly on the current produced by breakdown of a ture The gloves, right side out, shall be filled with tap water specimen under test This circuit breaking device should be and immersed in water to a depth in compliance with Table 6 designed to protect the test equipment under any conditions of for the test voltage to be used The water level during the test short circuit The equipment shall be inspected at least annually shall be the same inside and outside the glove The water inside to ensure that the general condition of the equipment is the glove that forms one test electrode shall be connected to acceptable and to verify the characteristics and accuracy of the one terminal of the voltage source by means of a chain or test voltages Calibrate the test equipment at least annually sliding rod that dips into the water The water in the tank with traceability to NIST (National Institute of Standards and outside the glove that forms the other electrode shall be Technology) connected directly to the other terminal of the voltage source The water shall be free of air bubbles and air pockets inside or 18.3.1.1 To eliminate damaging ozone and possible flash- outside the glove, and the exposed portion of the glove above over along the glove cuff, there should be a sufficient flow of the water line shall be dry Water used as electrodes shall have air into and around the glove and an exhaust system to a minimum conductance of 100 µS/cm adequately remove ozone from the test machine Consistent ozone cutting and checking during the test procedure should be NOTE 4—Both ac and dc voltage proof-test methods are included in this cause to ascertain the adequacy of the exhaust system section It is intended that one method be selected for the electrical tests The method selected shall be at the option of the purchaser, and the 18.3.1.2 Glove failure indicators or accessory circuits shall supplier should be so notified of the selection be designed to give positive indication of failure and shall require resetting by the operator before tests can be continued 18.2 Warning—It is recommended that the test apparatus be designed to afford the operator full protection in perfor- 18.4 AC Tests: mance of his duties Reliable means of de-energizing and 18.4.1 Voltage Supply and Regulation: grounding the high-voltage circuit shall be provided It is 18.4.1.1 The desired test voltage may be obtained most particularly important to incorporate a positive means of readily from a step-up transformer energized from a variable grounding the high-voltage section of dc test apparatus due to low-voltage source The transformer and its control equipment the likely presence of high-voltage capacitance charges at the shall be of such size and design that, with the test specimen in conclusion of the test the circuit, the crest factor (ratio of maximum to mean effective) of the test voltage shall differ by not more than 5 % 18.3 Test Equipment: from that of a sinusoidal wave over the upper half of the range 18.3.1 The test equipment used in the proof, acceptance, of the test voltage and dielectric breakdown tests shall be capable of supplying an 18.4.1.2 The accuracy of the voltage measuring circuit shall essentially stepless and continuously variable voltage to the be within 61 kV of the test voltage The ac voltage applied to test specimen Motor-driven regulating equipment is conve- the test specimen shall be measured with either an ac voltmeter nient and tends to provide uniform rate-of-rise to the test TABLE 6 Clearances—Cuff to Water Line A ,B AC DC Class of Proof Test Breakdown Proof Test Breakdown Glove 00 mm in mm in mm in mm in 0 1 38 11⁄2 38 11⁄2 38 11⁄2 51 2 2 3 38 11⁄2 38 11⁄2 38 11⁄2 51 2 4 38 11⁄2 64 21⁄2 51 2 102 4 64 21⁄2 76 3 76 3 127 5 89 31⁄2 102 4 102 4 152 6 127 5 165 61⁄2 153 6 178 7 A Permissible tolerance clearance – Cuff to water ±13 mm (±1⁄2 in.) B In those cases where atmospheric conditions make the specified clearances impractical, the clearances may be increased by a maximum of 25 mm (1 in.) 7 D120 − 22 (RMS or average responding) or a peak responding voltmeter 18.5.1.1 The dc test voltage shall be obtained from a dc calibrated to pk/SQRT2 using one of the following methods: source capable of supplying the required voltage The peak to (1) a voltmeter used in conjunction with a calibrated instrument peak ac ripple component of the dc proof-test voltage shall not transformer connected directly across the high-voltage circuit, exceed 2 % of the average voltage value under no-load (2) a calibrated electrostatic voltmeter connected directly conditions across the high-voltage circuit, or (3) an ac meter connected in series with appropriate high-voltage type resistors directly 18.5.1.2 Measure the dc proof-test voltage by a method that across the high-voltage circuit provides the average value of the voltage applied to the test specimen It is recommended that the voltage be measured by 18.4.1.3 The crest factor may be checked by the use of a the use of a dc meter connected in series with appropriate peak-reading voltmeter connected directly across the high- high-voltage type resistors across the high-voltage circuit An voltage circuit; or, if an electrostatic voltmeter or a voltmeter in electrostatic voltmeter of proper range may be used in place of conjunction with an instrument potential transformer is con- the dc meter-resistor combination The accuracy of the voltage nected across the high-voltage circuit, a standard sphere gap measuring circuit shall be within 61 kV of the test voltage may be sparked over and the corresponding voltage compared with the reading of the rms voltmeter 18.5.2 DC Proof Test: 18.4.1.4 The proof-test current shall be measured by insert- 18.5.2.1 Each glove shall be given a proof test in accor- ing a milliammeter in series with each individual glove The dance with the requirements of 11.1 The dc proof-test voltage reading should be taken near the end of the proof-test period shall be applied in the same manner as for ac proof tests except with a rate-of-rise of approximately 3000 V/s 18.4.2 AC Proof Tests: 18.4.2.1 Each glove shall be given a proof test in accor- 18.5.3 DC Breakdown Test: dance with the requirements of 11.1 The proof-test voltage shall be applied initially at a low value and increase at a 18.5.3.1 The dc breakdown tests shall be performed in the constant rate-of-rise of approximately 1000 V/s until the same way as ac breakdown tests except with a rate-of-rise of prescribed test voltage level is reached, or failure occurs The approximately 3000 V/s test period starts at the instant that the prescribed testing voltage is reached The applied voltage should be reduced to at 18.6 Ozone Resistance Test—The ozone resistance test shall least half value, unless an electrical failure has occurred, at the be made in accordance with the following method to ensure end of the test period before opening the test circuit conformance of Type II gloves with the requirements of 10.3 18.4.3 AC Breakdown Test: 18.4.3.1 Each sample selected in accordance with 13.2 shall 18.6.1 The ozone resistance test shall be made on a 100 mm be given a breakdown test as specified in 11.2 The voltage by 150 mm (4-in by 6-in.) specimen of the glove material shall be applied at a low value and increase at a constant prepared from a sample suitably conditioned by lying flat for rate-of-rise of approximately 1000 V/s until the prescribed 24 h The specimen should be draped over a 25 mm (1-in.) minimum breakdown voltage is reached or failure occurs The diameter metal tube of sufficient length to completely underlie maximum voltage observed prior to failure shall be considered the specimen, while possessing additional length for the as the breakdown voltage required mounting supports The metal tubing shall be electri- 18.4.4 AC Moisture Absorption/Proof Test: cally grounded The free ends of the specimen shall be clamped 18.4.4.1 Each sample selected in accordance with 13.2 shall beneath the tubing electrode so that an intimate contact is be given an AC moisture absorption/proof test as specified in established between the specimen and the tubing along the 11.3 Sample gloves that have passed the ac proof test upper half of the cylindrically-shaped electrode surface requirement of 18.4.2 shall be placed in the test equipment, immersed in water in accordance with 18.1 and soaked for 16 18.6.2 A piece of flat aluminum sheet foil, approximately 50 h Alternately, the gloves may be soaked by submerging mm by 100 mm (2 in by 4 in.), shall be placed over the draped completely in water without trapping air and then transferring specimen so as to provide adequate separation distance to them directly to the test equipment in accordance with 18.1 prevent flashover between the foil and the metal tubing An The gloves will be soaked for 16 continuous hours at room electrode wire shall be connected to the aluminum foil temperature Immediately after the soak period, the proof test voltage shall then be applied initially at a low value and 18.6.3 The outer electrode (metal foil) shall be energized to increased at a constant rate-of-rise of approximately 1000 V/s 15 kV ac (rms) from a stable 60-Hz source The 15 kV until the prescribed test voltage level is reached or failure potential may be derived from a suitably rated potential occurs The proof test current shall then be measured and transformer energized from its low-voltage winding through a recorded The applied voltage shall then be reduced to at least continuously variable autotransformer An overcurrent protec- half value, unless an electrical failure has occurred, before tive device should be incorporated into the low-voltage control opening the test circuit circuit in case of an electrical breakdown NOTE 5—If an alternate method is used, ensure that the clearance area 18.6.4 The ozone resistance of the specimen should be is dry to avoid flashover determined qualitatively, by inspection, after a 1-h exposure period in the test apparatus at the 15 kV potential At least two 18.5 DC Tests: specimens from each sample glove selected in accordance with 18.5.1 Voltage Supply and Regulation: 13.2 shall be tested Two specimens should not be taken from the same section of the sample glove NOTE 6—The rate of ozone degradation is inversely proportional to the relative humidity of the surrounding air Empirical data indicate, however, that visible ozone effects will be evident over a broad range of ambient humidities under these test conditions 8 D120 − 22 19 Chemical and Physical Tests shall have an opening 25 mm (1.0 in.) in diameter to provide a fixed free area through which the specimen can elongate 19.1 Chemical Tests: while being subjected to the pressure of the needle point The 19.1.1 The composition of the rubber hydrocarbon portion edges of the openings should be rounded to a radius of of Type I gloves may be determined in accordance with the test approximately 0.8 mm (0.03 in.) The needle shall be made method in Methods D297 from 5 mm (0.19-in.) diameter Type 304 stainless steel rod The rod should be machined at one end to produce a taper with 19.2 Physical Tests: an included angle of 12° with the tip of the tapered end rounded 19.2.1 Physical tests should be performed to determine the to a radius of 0.8 mm (0.03 in.) The needle shall be initially physical requirements specified in Section 10 The glove positioned perpendicularly to the specimen so that the point samples should be conditioned by storing in a flat position for contacts the specimen through the small hole in the plate The 24 h at a room temperature of 23 6 4 °C (73 6 7 °F) needle shall be driven into and through the specimen at a 19.2.2 The tensile strength, tensile stress at 200 % of continuous rate of approximately 8.3 mm/s (20 in./min) The elongation, and tension set tests shall be performed in accor- maximum force required to perform the puncturing operation dance with Test Methods D412, except for elongation time shall be measured to the nearest 2 N (0.5 lbf) The puncture The test specimen shall conform in dimensions to Die C The resistance shall be calculated by dividing the puncturing force elongation in the tension set shall be 400 % with grip separa- by the specimen thickness and recorded in units of newtons per tion at a rate of 500 mm 6 50 mm (20 in 6 2)/min metre (or pounds-force per inch) 19.2.3 The tear resistance test shall be performed in accor- dance with Test Method D624 The test specimen shall 19.2.5 The durometer test shall be performed in accordance conform to the dimensions of Die C with Test Method D1415 or Test Method D2240, using a Type 19.2.4 The puncture resistance test shall be performed to A durometer determine the ability of the glove material to withstand puncture 19.2.6 The accelerated aging tests shall be performed in 19.2.4.1 A glove specimen shall be cut to fit between the accordance with Test Method D573 After being subjected to a opposing faces of two flat metal plates having concentric temperature of 70 6 2 °C (158 6 3.6 °F) in circulating air for openings The thickness of each test specimen shall be mea- 7 days, the tensile strength and elongation of the specimen sured at its approximate center using a micrometer having the shall not be less than 80 % of the original characteristics described in Test Methods D412 One of the plates shall have a circular opening 6 mm (0.25 in.) in diameter 20 Keywords to allow the passage of a stainless steel needle The other plate 20.1 electrical insulating gloves; lineman; lineman protec- tive equipment ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned in this standard Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk of infringement of such rights, are entirely their own responsibility This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and if not revised, either reapproved or withdrawn Your comments are invited either for revision of this standard or for additional standards and should be addressed to ASTM International Headquarters Your comments will receive careful consideration at a meeting of the responsible technical committee, which you may attend If you feel that your comments have not received a fair hearing you should make your views known to the ASTM Committee on Standards, at the address shown below This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website (www.astm.org) Permission rights to photocopy the standard may also be secured from the Copyright Clearance Center, 222 Rosewood Drive, Danvers, MA 01923, Tel: (978) 646-2600; http://www.copyright.com/ 9

Ngày đăng: 10/03/2024, 04:14

Từ khóa liên quan

Tài liệu cùng người dùng

Tài liệu liên quan